EtherNet/IP node. User-defined fault actions to determine how the embedded EtherNet/IP adapter and its host PowerFlex 525 drive respond to: – I/O messaging communication disruptions (Comm Flt Action) – Controllers in idle mode (Idle Flt Action). Automatic Device Configuration (ADC) is an RSLogix 5000 (version 20.

34

Rockwell Automation Publication 520-QS001A-EN-E - March 2014

Powerflex 525 User Manual Pdf

PowerFlex 520-Series Adjustable Frequency AC Drive

The following PowerFlex 520-series drive parameters are used to configure the drive to operate on a DSI network.

PowerFlex 525 Embedded EtherNet/IP

This section contains only basic information to setup an EtherNet/IP connection with your PowerFlex 525 drive. For
comprehensive information about EtherNet/IP (single and dual-port) and how to use it, see the following publications:

PowerFlex 525 Embedded EtherNet/IP Adapter User Manual, publication

520COM-UM001

.

PowerFlex 25-COMM-E2P Dual-Port EtherNet/IP Adapter User Manual, publication

520COM-UM003

.

Connecting the Adapter to the Network

1. Remove power from the drive.

2. Remove the drive control module cover.

3. Use static control precautions.

4. Connect one end of an Ethernet cable to the EtherNet/IP network.

5. Route the other end of the Ethernet cable through the bottom of the PowerFlex 525 drive, and insert the cable’s plug

into the embedded EtherNet/IP adapter’s mating socket.

Configuring Parameters for DSI Network

Parameter

Description

P046 [Start Source 1]

Set to 3 “Serial/DSI” if Start is controlled from the network

P047 [Speed Reference1]

Set to 3 “Serial/DSI” if Speed Reference is controlled from the network.

525

C123 [RS485 Data Rate]

Sets the data rate for the RS485 (DSI) port. All nodes on the network must be set to the same data rate.

A page of data in WWS contains a maximum of 100 entries. Parameter nameType/ValueCardinalityDescriptionValidationsTotalResultsdecimal (12, 0) 00.1The total number of results that have been returned from your request.TotalPagesdecimal (12, 0) 00.1The total number of pages that exist for your request. For example, set Page = 2 to retrieve the second page of data.Note: If you set the page parameter, you must also specify the 'AsOfEntryDate' to ensure that the result set remains the same between your requests.Countdecimal (3, 0) 00.1Sets the number of objects to return within each response page (Min = 1, Max = 999, Default = 100 if not set). Any values you set must be between 1-999.ValidationDescriptionPage Number cannot be zero.Page number cannot be zero.AssignUser-BasedSecurityGroupsResponseGroup part of. Urban security group skip 7182m user manual instructions.

C124 [RS485 Node Addr]

Sets the node address for the drive on the network. Each device on the network requires a unique node address.

C125 [Comm Loss Action]

Selects the drive’s response to communication problems.

C126 [Comm Loss Time]

Sets the time that the drive will remain in communication loss before the drive implements C125 [Comm Loss Action].

C127 [Comm Format]

Sets the transmission mode, data bits, parity, and stop bits for the RS485 (DSI) port. All nodes on the network must be set to the same setting.

C128 [Comm Write Mode]

Set to 0 “Save” when programming drive.
Set to 1 “RAM only” to only write to volatile memory.

ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death. Remove
power from the drive, and then verify power has been discharged before connecting the embedded EtherNet/IP adapter to the
network.

1 (Front)

1 (Front)

Powerflex 525 Embedded Ethernet Ip Adapter User Manual

1 (Front)
2 (Rear)

00:00:BC:2E:69:F6

Esc

Sel

Ethernet switch

1769-L36ERM CompactLogix controller
with embedded EtherNet/IP bridge

PowerFlex 525 with embedded
EtherNet/IP adapter (Frame A shown)

Advertising
This manual is related to the following products:

Adapter

Popular Brands
Popular manuals
34Rockwell Automation Publication 520-QS001A-EN-E - March 2014
PowerFlex 520-Series Adjustable Frequency AC Drive
The following PowerFlex 520-series drive parameters are used to configure the drive to operate on a DSI network.
This section contains only basic information to setup an EtherNet/IP connection with your PowerFlex 525 drive. For
comprehensive information about EtherNet/IP (single and dual-port) and how to use it, see the following publications:
PowerFlex 525 Embedded EtherNet/IP Adapter User Manual, publication 520COM-UM001
PowerFlex 25-COMM-E2P Dual-Port EtherNet/IP Adapter User Manual, publication 520COM-UM003

Profinet

Connecting the Adapter to the Network
2.Remove the drive control module cover.
4.Connect one end of an Ethernet cable to the EtherNet/IP network.
5.Route the other end of the Ethernet cable through the bottom of the PowerFlex 525 drive, and insert the cable’s plug
into the embedded EtherNet/IP adapter’s mating socket.
ParameterDescription
P046 [Start Source 1]Set to 3 “Serial/DSI” if Start is controlled from the network
P047 [Speed Reference1]Set to 3 “Serial/DSI” if Speed Reference is controlled from the network.
C123 [RS485 Data Rate]Sets the data rate for the RS485 (DSI) port. All nodes on the network must be set to the same data rate.
C124 [RS485 Node Addr]Sets the node address for the drive on the network. Each device on the network requires a unique node address.
C125 [Comm Loss Action]Selects the drive’s response to communication problems.
C126 [Comm Loss Time]Sets the time that the drive will remain in communication loss before the drive implements C125 [Comm Loss Action].
C127 [Comm Format]Sets the transmission mode, data bits, parity, and stop bits for the RS485 (DSI) port. All nodes on the network must be set to the same setting.
C128 [Comm Write Mode]Set to 0 “Save” when programming drive.
Set to 1 “RAM only” to only write to volatile memory.
ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death. Remove
power from the drive, and then verify power has been discharged before connecting the embedded EtherNet/IP adapter to the
2 (Rear)
Esc
1769-L36ERM CompactLogix controller
PowerFlex 525 with embedded